Instrumentation basics · 1.4

Range, span, accuracy, repeatability and turndown, with the numbers

25 October 2026 · 10 min read · IEC 60770-1, IEC 61298-2

In short

Every datasheet has a range and an accuracy line, and both are easy to fill in wrongly. This article defines the terms the way vendors use them, then works through one transmitter specification to show what a "0.075 % accurate" instrument really delivers in the field.

Where this matters

How it works

Limits, range and span

TermMeaningExample
URL / LRLUpper and lower range limit: the most the sensor can be set to0–70 bar
URV / LRVUpper and lower range value: the calibrated 20 mA and 4 mA points0–10 bar
SpanURV − LRV10 bar
TurndownURL ÷ span70 ÷ 10 = 7 : 1
Maximum turndownURL ÷ minimum allowed span (vendor limit)often 100 : 1 or more

A suppressed zero (LRV above zero, such as 5–10 bar) and an elevated zero (LRV below zero, such as −2 to +3 m in DP level) are both normal. They are common in level measurement with wet legs (article 5.1).

Accuracy terms

"% of what?"

% of span · % of reading (rate) · % of URL · % of full scale

Pressure and temperature transmitters usually quote % of span. Magnetic and Coriolis flowmeters usually quote % of reading. Gauges quote an accuracy class as % of full scale. The difference is large at low readings. An error of ±0.5 % of span at 20 % of range is ±0.5 / 0.2 = ±2.5 % of reading.

Total probable error

The accuracy on the front of a brochure is at reference conditions: about 20 °C, steady and freshly calibrated. In the field, other effects add to it. Because they are independent, they are combined by root-sum-square:

TPE = √( Eref² + Etemp² + Estatic² + … )

Eref is the reference accuracy, Etemp the ambient temperature effect over the expected change, and Estatic the static (line) pressure effect, which applies to DP transmitters. Stability is assessed separately against the calibration interval.

What the standards and practice say

Worked example: what "0.075 %" really means

Here is an example gauge pressure transmitter specification, of the kind found on vendor datasheets:

Specification itemExample value
Sensor URL70 bar
Reference accuracy±0.075 % of span
Ambient temperature effect±(0.025 % URL + 0.125 % span) per 28 °C
Expected ambient change from calibration20 °C

Case 1, ranged 0–10 bar (turndown 7 : 1).

Case 2, same sensor ranged 0–2 bar (turndown 35 : 1).

RangeTurndownBrochure accuracyTotal probable error
0–10 bar7 : 10.075 %0.23 % of span
0–2 bar35 : 10.075 %0.72 % of span

What this example shows

When it fails: the fixes in order

  1. Pick a sensor whose URL suits the range. This is the cheapest accuracy improvement there is.
  2. Reduce the ambient change. Sunshades, enclosures or calibrating near the operating temperature all help.
  3. Specify the accuracy class needed. Premium "0.04 %" transmitters exist, but they help only if the other terms are also small.
  4. Shorten the calibration interval where stability is the limit.
  5. For flow, check the % of reading at minimum flow, not just at full scale.

Common mistakes

Checklist

Quick reference

Further reading

The transmitter specification is an illustrative example in the usual vendor form, not a particular product. Use the actual vendor's specification, including its footnotes on turndown, for design. IEC is named for identification only.