Instrumentation basics · 1.5

Gauge, absolute and differential pressure, and the units that trip people up

25 October 2026 · 9 min read · ISO 80000-4, IEC 60770-1

In short

Pressure is the most-measured variable in most plants, and it comes with a hidden trap. The same number means different things depending on what it is referenced to. Before choosing a pressure instrument, you need to know what reference the process data uses, what the instrument measures, and what the control system expects.

Where this matters

How it works

The three references

Pabs = Pgauge + Patm ΔP = Phigh − Plow
TypeReferenceTypical suffixTypical use
GaugeLocal atmosphere (sensor vented)barg, psig, kPa(g)Most process pressures, equipment protection
AbsolutePerfect vacuum (sealed reference)bara, psia, kPa(a)Vacuum, gas density, vapour pressure, barometric
DifferentialA second process connectionbar(d), mbar, kPaFlow (orifice), level (DP), filter or strainer loss
Sealed gaugeA fixed sealed reference, near 1 atmbar(sg)Hostile or submerged locations where venting is impractical

Vacuum is often written as a negative gauge pressure (−0.5 barg) or as "mbar vacuum". Always convert it to absolute before doing calculations.

Atmospheric pressure changes

Atmospheric pressure varies by a few percent with the weather and falls with altitude. A common approximation from the International Standard Atmosphere is:

Patm ≈ 101.325 × (1 − 2.25577 × 10⁻⁵ × h)5.25588 [kPa, h in m]

At sea level that gives 1.013 bar, and at 1,500 m it gives 0.846 bar, 16 % lower.

Units

UnitEqual toNote
1 bar100 kPa = 14.504 psiCommon in process work, not SI but accepted
1 kg/cm²0.980665 barOlder drawings, often used as if it were 1 bar
1 atm1.01325 barStandard atmosphere
1 mmH₂O9.80665 PaLow DP and draft (at 4 °C water)
1 inH₂O≈ 249 PaThe reference temperature (4 °C, 60 °F or 68 °F) changes the fourth digit
1 MPa10 barCommon on Asian and European codes

What the standards and practice say

Worked example: one missing "a" in a gas flow

A gas flow is measured by an orifice plate with pressure compensation. The process data sheet gives "operating pressure 5 bar".

InputValue
Real line pressure5.000 barg = 6.013 bara (at sea level)
Compensation configured with5.000 "bar", taken as absolute
Flow equationMass flow ∝ √(ΔP × ρ), with ρ ∝ Pabs for an ideal gas

Step 1, density error. Taking 5.000 instead of 6.013 bara makes the calculated density 5.000 / 6.013 = 0.832 of the true value, which is 16.8 % low.

Step 2, flow error. Flow scales with the square root of density: √0.832 = 0.912, so the flow reads 8.8 % low.

Step 3, the same plant at 1,500 m. The real absolute pressure is 5.000 + 0.846 = 5.846 bara. Even an engineer who adds 1.013 by habit gets 6.013, and is 2.9 % high on density and 1.4 % high on flow.

Pressure usedTrue valueFlow error
5.000 (gauge taken as absolute)6.013 bara−8.8 %
6.013 (sea-level atmosphere added)5.846 bara at 1,500 m+1.4 %
5.846 (local atmosphere added)5.846 bara0 %

What this example shows

When it fails: the fixes in order

  1. Ask the source. Ask the process engineer whether a number is gauge or absolute, and write the answer on the data.
  2. Choose the sensor type to match the use. Use absolute for vacuum and compensation, gauge for protection and general indication, and DP for flow, level and filters.
  3. Fix the units in the DCS. The engineering units text on the tag should carry g, a or d.
  4. Use the site's atmospheric pressure in all conversions.
  5. Re-check set points after any change of reference.

Common mistakes

Checklist

Quick reference

Further reading

The flow example uses the ideal-gas relation to show the size of the effect. Real compensation should use the project's gas properties, including the compressibility factor Z. ISO, IEC, ASME and EN are named for identification only.