Pressure · 2.1

Pressure sensors: strain gauge, capacitive, piezoresistive and resonant

26 October 2026 · 9 min read · IEC 60770-1, IEC 61298

In short

Open any pressure transmitter and you find a small sensor behind a thin metal diaphragm. How that sensor turns deflection into a signal explains most of the differences between transmitter models. It shows why one drifts and another doesn't, and why one survives a pressure spike that ruins another.

Where this matters

How it works

The common front end

Process pressure acts on a thin isolating diaphragm, usually 316L stainless, Hastelloy C-276, Monel, tantalum or gold-plated. Behind it, a sealed fill fluid, usually silicone oil or an inert fluorocarbon for oxygen service, carries the pressure to the sensing element. The isolating diaphragm keeps the process away from the delicate sensor.

1. Metal-foil or thin-film strain gauge

Strain gauges are bonded or deposited on a metal diaphragm. As it flexes, their resistance changes. Four gauges form a Wheatstone bridge:

Vout = GF × ε × Vex (full bridge, four active arms)

GF is the gauge factor (about 2 for metal foil), ε is the strain (m/m) and Vex is the excitation voltage. The signal is small: at 1,000 µε and 10 V excitation, Vout = 2 × 0.001 × 10 = 20 mV. Strain gauges are robust and common in pressure gauges, OEM sensors and high-pressure transmitters.

2. Piezoresistive silicon

The resistors are diffused into a silicon diaphragm. The gauge factor is 50–100 times that of metal foil, so the signal is large and low ranges are easy. Silicon is temperature-sensitive, so the electronics compensate using an on-chip temperature measurement. This is the most common technology in modern transmitters.

3. Capacitive

The diaphragm forms one plate of a capacitor. Pressure changes the gap d, and the capacitance follows:

C = ε0 εr A / d

Here ε0 is the permittivity of vacuum, εr the relative permittivity of the fill, and A the plate area. In a differential cell, the sensing diaphragm sits between two fixed plates, so pressure increases one capacitance and decreases the other. The ratio is very stable and gives good overpressure tolerance, because the diaphragm bottoms out on a backstop. This is widely used for DP transmitters.

4. Resonant (silicon or quartz)

A tiny beam is driven at its natural frequency, which changes with the stress the diaphragm puts on it. Frequency is measured digitally, so there is no analogue drift. This gives the best long-term stability and is used for high-accuracy and reference work.

Comparison

TechnologyStrengthsWatch out forTypical use
Metal strain gaugeRugged, high pressure, simpleSmall signal, more driftGauges, OEM, very high pressure
Piezoresistive siliconLarge signal, low ranges, low costNeeds temperature compensationGeneral-purpose transmitters
CapacitiveStable, good overpressure, good DPSensitive to fill lossDP flow and level, gauge and absolute
ResonantBest stability, digital outputCostHigh accuracy, fiscal, reference

What the standards and practice say

Worked example: choosing a sensor for three services

ServiceKey needGood fitWhy
Hydraulic power unit, 0–400 bar, pulsatingRobustnessMetal strain gaugeThick metal diaphragm survives spikes. The signal is ample at high range.
Draft on a fired heater, −5 to +5 mbarLow rangePiezoresistive or capacitive DPLarge signal at low pressure.
Gas sales line, 70 barg, 5-year calibration intervalStabilityResonantFrequency output with very low drift.

Signal size check. A strain-gauge bridge at 10 V excitation and 1,000 µε gives 20 mV. A silicon bridge with a gauge factor around 100 would give about 1 V for the same strain. That is why silicon suits the draft measurement, while metal foil is fine at 400 bar where strain is not the problem.

What this example shows

When it fails: the fixes in order

  1. Drift: check for hydrogen permeation or a temperature cycle first. Then consider a more stable technology or a gold-plated diaphragm.
  2. Damage after spikes: fit a snubber, check the overpressure rating, and consider a sensor with a mechanical backstop.
  3. Noisy low-range reading: use a lower-URL sensor rather than ranging down a high one (article 1.4).
  4. Corroded diaphragm: change the wetted material, or add a diaphragm seal (article 2.4).

Common mistakes

Checklist

Quick reference

Further reading

Performance rankings are typical, not absolute. Individual products vary, so compare the vendors' stated specifications line by line. IEC is named for identification only.