DP transmitters and manifolds: static pressure, 3-valve and 5-valve sequences

26 October 2026 · 9 min read · IEC 60770-1, ISO 2186

In short

DP transmitters measure flow across orifice plates, level in vessels and pressure loss across filters. They are the most demanding pressure instrument to handle in the field, because their range may be a few hundred millibar while each side sits at tens of bar.

Where this matters

How it works

ΔP = PH − PL static (line) pressure ≈ PL

The sensing cell has a high side and a low side. The cell's maximum working pressure (MWP, or static pressure rating) must exceed the design pressure. Its one-sided overpressure limit is what it survives if full pressure reaches one side only. Good cells have a mechanical backstop for this, but repeated events still shift the zero.

Manifolds

TypeValvesUse
3-valveHigh block, low block, equaliserMost DP services
5-valveAs 3-valve, plus two vent or test valves (or a double equaliser with a vent)Gas and hazardous fluids, venting and in-situ testing without breaking connections

Safe sequences (3-valve)

Putting in service: 1) equaliser open, both blocks closed; 2) open the high block; 3) close the equaliser; 4) open the low block.

Taking out of service: 1) close the low block; 2) open the equaliser; 3) close the high block; 4) vent through the drain or test valves.

Zero check in service: close the low block, open the equaliser, read and zero at line pressure, close the equaliser, and reopen the low block.

The sequences ensure that the cell never sees line pressure on one side with the other side at atmosphere. In gas service, vent to a safe location. A 5-valve manifold lets you do that without loosening fittings.

Static pressure effect

A cell deforms slightly under static pressure, and that shifts the zero and the span. Vendors quote it, typically as a % of URL per 100 bar for zero. The zero part can be trimmed at line pressure. The span part is usually smaller and is corrected in the factory.

What the standards and practice say

Worked example: a filter DP transmitter

InputValue
Line pressure / design40 / 50 barg
DP range0–500 mbar
Sensor URL2.5 bar
Static effect on zero (example spec)±0.1 % of URL per 100 bar

Step 1, rating. The static pressure rating must be at least 50 barg. A standard 100 or 160 bar class cell is suitable.

Step 2, static zero shift at 40 bar. 0.1 % × 2.5 bar × 40/100 = 0.001 bar = 1 mbar, which is 0.2 % of the 500 mbar span. Zeroing at line pressure removes most of it.

Step 3, what a wrong sequence does. Opening the low block first, with the equaliser closed and the high side vented, puts 40 bar on one side of a cell ranged 0.5 bar. That is 80 times the span, or 16 times the URL. The cell depends entirely on its one-sided overpressure rating.

SituationPressure seen by the cellResult
Correct sequence≤ 0.5 bar DPNormal
Zero not trimmed at line pressure+1 mbar offset0.2 % error
Wrong sequence40 bar one sideZero shift, possible damage

What this example shows

When it fails: the fixes in order

  1. Zero offset: zero at line pressure with the equaliser open.
  2. A shift after maintenance: suspect a one-sided overpressure. Recalibrate, and retrain on the sequence.
  3. A leaking equaliser reads low: a passing equaliser bleeds DP away. Test it by closing the blocks and watching the reading.
  4. An erratic reading: look at the impulse lines next (article 2.6).

Common mistakes

Checklist

Quick reference

Further reading

The static effect figure is an illustrative specification in the usual vendor form. Use the actual product data and the site's valve operating procedures. IEC and ISO are named for identification only.