Pressure · 2.4
Diaphragm seals: when you need them and the temperature errors they bring
26 October 2026 · 9 min read · IEC 60770-1, EN 837-1
In short
- A diaphragm seal keeps the process away from the transmitter. A fill fluid carries the pressure, either close-coupled or through a capillary.
- Seals add errors. The fill's own head (ρfill g h) and the change of that head with temperature are the big ones.
- The head is fixed and can be calibrated out. The temperature change cannot, and it can be several percent of a level span.
- Keep capillaries short, equal and at the same temperature, and use the largest seal diameter that fits.
Some fluids should never reach a transmitter's sensor: slurries that block, corrosive acids, polymers that set, hot fluids or anything that must stay sterile. A diaphragm seal solves that, but it turns a simple pressure measurement into a small hydraulic system, with errors of its own.
Where this matters
- Corrosive, viscous, crystallising or solids-laden fluids that would block or attack an impulse line.
- High temperatures beyond the transmitter's limit.
- Hygienic service needing flush, cleanable connections.
- DP level on tall vessels with remote seals, where the temperature error is largest.
How it works
A thin flexible diaphragm sits flush with the process. Behind it a sealed fill fluid (silicone oil, a high-temperature oil, an inert fluorocarbon, or a food-grade oil) carries the pressure to the transmitter. The connection is either direct mount (close-coupled) or through a capillary, a thin armoured tube several metres long.
Head of the fill
ρfill is the fill density (kg/m³), g = 9.80665 m/s² and h is the vertical distance (m) between the seal and the transmitter. A seal above the transmitter adds pressure, and one below subtracts it. In a two-seal DP level system, the difference in height between the two seals gives a fixed offset that is set in the calibration.
Temperature effects
- Density change: the fill's density falls as it warms (about 0.1 %/°C for silicone oil), so the head changes. This is the largest error for tall remote-seal systems.
- Volume change: the fill expands and pushes against the diaphragm. A stiffer (smaller) diaphragm turns that into a larger false pressure, so large diaphragms are better.
- Response time: long, thin capillaries and viscous fills slow the response, especially in cold weather.
What the standards and practice say
- Vendors give seal systems their own total error and response time, calculated for the specific seal, fill, capillary length and temperatures. Ask for that calculation for each critical application.
- EN 837-1 covers gauges, and seals for gauges follow vendor and application standards. IEC 60770-1 covers the transmitter.
- Choose fill for the process temperature range and vacuum. Some fills boil off under vacuum at high temperature.
- For DP level, tuned systems (matched capillaries) and electronic remote sensors (two transmitters linked digitally) reduce or remove capillary errors.
Worked example: DP level on a 5 m tank with two seals
| Input | Value |
|---|---|
| Seal spacing (vertical) | 5 m |
| Process | Water-like, ρ = 1,000 kg/m³ |
| Fill | Silicone, ρfill = 930 kg/m³, density change ≈ 0.096 %/°C |
| Temperature swing of the low-side capillary run | 30 °C (night to midday sun) |
Step 1, span. The level range is 0–5 m, so the span is 1,000 × 9.80665 × 5 = 49,033 Pa = 490 mbar.
Step 2, fill head. 930 × 9.80665 × 5 = 45,601 Pa = 456 mbar on the low side. This is constant, so it is taken out by the calibration (elevated zero).
Step 3, temperature error. The density change over 30 °C is 0.096 % × 30 = 2.9 %. The head therefore changes by 0.029 × 456 = 13 mbar.
Step 4, as a share of span. 13 / 490 = 2.7 % of the level span, or about 13 cm of level from the sun alone.
| Error source | Size | Can it be calibrated out? |
|---|---|---|
| Fill head (456 mbar) | 93 % of span | Yes, fixed offset |
| Fill density with temperature | ≈ 2.7 % of span | No, it changes all day |
| Transmitter reference accuracy | ≈ 0.1 % of span | Small by comparison |
What this example shows
- The seal system, not the transmitter, sets the accuracy.
- Tall vessels in the sun are the worst case. Trace-heat or insulate both capillaries together, or use an electronic remote sensor.
- Ask for the vendor's seal-system error calculation before you accept a seal for a trip or an inventory measurement.
When it fails: the fixes in order
- Shorten or remove the capillary. Direct-mount where you can.
- Keep both capillaries together, the same length and at the same temperature (shade, insulation, tracing).
- Use a larger diaphragm to reduce the volume-change error.
- Use an electronic remote sensor system on tall vessels.
- Choose a lower-expansion or more suitable fill for the temperature range.
Common mistakes
- Specifying seals by habit for clean services that do not need them.
- Long capillaries coiled in the sun on one side only.
- Small seal diameters on low ranges.
- Forgetting the fill head when ranging, which gives a large zero error at commissioning.
- A fill fluid unsuitable for vacuum at temperature.
- Kinked or damaged capillaries. They cannot be repaired in the field.
Checklist
- A seal is really needed: corrosive, solids, viscous, hot or hygienic.
- The diaphragm material and seal type suit the process.
- The fill suits the minimum and maximum temperature and vacuum.
- The capillary length is as short as possible, and both sides are equal.
- The vertical heights between seals and transmitter are recorded for calibration.
- The seal-system total error and response time come from the vendor.
- The ambient temperature swing is stated, and the capillaries are protected.
- Critical tall-vessel levels consider an electronic remote sensor.
Quick reference
- Head: ΔP = ρfill g h (≈ 91 mbar per metre for silicone at 930 kg/m³).
- Temperature error ≈ (density change %/°C × ΔT) × fill head.
- Silicone: density change about 0.1 %/°C.
- Rules: short, equal, same temperature, big diaphragm.
Further reading
- EN 837-1, Pressure gauges: Bourdon tube pressure gauges (for gauges with seals)
- IEC 60770-1, Transmitters for use in industrial-process control systems: methods for performance evaluation
- In this series: 2.3 DP transmitters and manifolds · next, 2.5 Pressure gauges · later, 5.1 DP level with wet and dry legs
The fill density and its temperature coefficient are typical values for silicone oil. Use the vendor's data for the actual fill and their seal-system calculation for design. EN and IEC are named for identification only.