Pressure · 2.4

Diaphragm seals: when you need them and the temperature errors they bring

26 October 2026 · 9 min read · IEC 60770-1, EN 837-1

In short

Some fluids should never reach a transmitter's sensor: slurries that block, corrosive acids, polymers that set, hot fluids or anything that must stay sterile. A diaphragm seal solves that, but it turns a simple pressure measurement into a small hydraulic system, with errors of its own.

Where this matters

How it works

A thin flexible diaphragm sits flush with the process. Behind it a sealed fill fluid (silicone oil, a high-temperature oil, an inert fluorocarbon, or a food-grade oil) carries the pressure to the transmitter. The connection is either direct mount (close-coupled) or through a capillary, a thin armoured tube several metres long.

Head of the fill

ΔPhead = ρfill × g × h

ρfill is the fill density (kg/m³), g = 9.80665 m/s² and h is the vertical distance (m) between the seal and the transmitter. A seal above the transmitter adds pressure, and one below subtracts it. In a two-seal DP level system, the difference in height between the two seals gives a fixed offset that is set in the calibration.

Temperature effects

What the standards and practice say

Worked example: DP level on a 5 m tank with two seals

InputValue
Seal spacing (vertical)5 m
ProcessWater-like, ρ = 1,000 kg/m³
FillSilicone, ρfill = 930 kg/m³, density change ≈ 0.096 %/°C
Temperature swing of the low-side capillary run30 °C (night to midday sun)

Step 1, span. The level range is 0–5 m, so the span is 1,000 × 9.80665 × 5 = 49,033 Pa = 490 mbar.

Step 2, fill head. 930 × 9.80665 × 5 = 45,601 Pa = 456 mbar on the low side. This is constant, so it is taken out by the calibration (elevated zero).

Step 3, temperature error. The density change over 30 °C is 0.096 % × 30 = 2.9 %. The head therefore changes by 0.029 × 456 = 13 mbar.

Step 4, as a share of span. 13 / 490 = 2.7 % of the level span, or about 13 cm of level from the sun alone.

Error sourceSizeCan it be calibrated out?
Fill head (456 mbar)93 % of spanYes, fixed offset
Fill density with temperature≈ 2.7 % of spanNo, it changes all day
Transmitter reference accuracy≈ 0.1 % of spanSmall by comparison

What this example shows

When it fails: the fixes in order

  1. Shorten or remove the capillary. Direct-mount where you can.
  2. Keep both capillaries together, the same length and at the same temperature (shade, insulation, tracing).
  3. Use a larger diaphragm to reduce the volume-change error.
  4. Use an electronic remote sensor system on tall vessels.
  5. Choose a lower-expansion or more suitable fill for the temperature range.

Common mistakes

Checklist

Quick reference

Further reading

The fill density and its temperature coefficient are typical values for silicone oil. Use the vendor's data for the actual fill and their seal-system calculation for design. EN and IEC are named for identification only.