Pressure · 2.5
Pressure gauges to EN 837: accuracy class, scale range, safety case and accessories
26 October 2026 · 9 min read · EN 837-1, EN 837-2, EN 837-3
In short
- A gauge's accuracy class is its maximum error as a percentage of full scale: class 1.0 on 0–16 bar is ±0.16 bar anywhere on the dial.
- Choose the scale so that the working pressure is at most ¾ of full scale for steady pressure and ⅔ for fluctuating pressure.
- For gas and high-pressure service, use the S3 safety pattern: solid front, blow-out back.
- Add a siphon for steam, a snubber or liquid filling for pulsation, and a diaphragm seal for corrosive or clogging fluids.
The humble pressure gauge is the instrument operators trust most, because it needs no power and no screen. It is also often specified by copying a line from the last project. EN 837 gives clear rules, and following them avoids gauges that are unreadable, inaccurate or dangerous when they fail.
Where this matters
- Local indication during start-up, maintenance and when the DCS disagrees with the field.
- Pump and compressor discharge, where pulsation destroys gauges quickly.
- Steam lines, where hot condensate can damage the Bourdon tube.
- Gas at high pressure, where a ruptured tube can blow out the dial window towards the person reading it.
How it works
Most gauges use a Bourdon tube: a curved, flattened tube that straightens slightly under pressure and drives the pointer through a gear movement (EN 837-1). For low pressures and corrosive fluids, diaphragm (plate) gauges are used (EN 837-3), and for very low gas pressures, capsule gauges.
Accuracy class
| Class | Error on 0–16 bar | Typical use |
|---|---|---|
| 0.6 | ±0.096 bar | Test gauges |
| 1.0 | ±0.16 bar | Process gauges, 100 mm and larger |
| 1.6 | ±0.26 bar | General service |
| 2.5 | ±0.40 bar | Small dials, utilities |
The error is fixed in bar, so it is a larger share of a small reading. This is one reason not to oversize the scale.
What the standards and practice say
- EN 837-1 covers Bourdon tube gauges: classes, sizes, cases and tests. EN 837-3 covers diaphragm and capsule gauges.
- EN 837-2 gives selection and installation recommendations. The working pressure should not exceed ¾ of full scale for steady pressure, or ⅔ for fluctuating pressure.
- Safety pattern (S3): a solid baffle between the tube and the dial, and a blow-out back, so that a rupture vents backwards, away from the reader. This is usually required for gas and for high pressure.
- Standard dial sizes are 63, 100 and 160 mm. 100 mm is the usual process size.
- Liquid filling (glycerine or silicone) damps pointer vibration and lubricates the movement in pulsating service.
Accessories
| Accessory | When |
|---|---|
| Siphon (pigtail or U-tube) | Steam and hot vapours: holds a condensate seal so hot steam doesn't reach the tube |
| Snubber or pulsation damper | Pump discharge, reciprocating compressors, hydraulic systems |
| Overpressure protector | Where pressure can exceed the scale, e.g. a low-range gauge on a higher-pressure line |
| Diaphragm seal | Corrosive, viscous or clogging fluids (article 2.4) |
| Gauge valve or 2-valve manifold | Isolation, venting and testing without a shutdown |
Worked example: a pump discharge gauge
| Input | Value |
|---|---|
| Normal / maximum pressure | 6 / 8 barg, pulsating |
| Fluid | Water at 40 °C |
| Accuracy needed | To about ±0.2 bar |
Step 1, scale. The pressure is pulsating, so the working value should be at most ⅔ of full scale. For 8 barg maximum, full scale must be at least 8 / (2/3) = 12 bar. The next standard scale is 0–16 bar. On a 0–10 bar dial, 8 barg would be at 80 %, too high for pulsating service.
Step 2, class. Class 1.0 on 0–16 bar gives ±0.16 bar. That meets ±0.2 bar. Class 1.6 (±0.26 bar) would not.
Step 3, case and accessories. Water at 8 barg does not need an S3 case on a strict reading, but many specifications require it for all process gauges. Pulsation calls for a liquid-filled case and a snubber.
| Option | Max at | Error | Result |
|---|---|---|---|
| 0–10 bar, class 1.6 | 80 % | ±0.16 bar | Too close to full scale for pulsation |
| 0–16 bar, class 1.6 | 50 % | ±0.26 bar | Accuracy not met |
| 0–16 bar, class 1.0, filled, snubber | 50 % | ±0.16 bar | Meets both |
What this example shows
- Pulsation decides the scale (⅔ rule), and the scale then decides the class needed.
- Accessories are part of the specification, not an afterthought.
- Standard scales are 1, 1.6, 2.5, 4, 6, 10, 16, 25… bar, so round up to the next one.
When it fails: the fixes in order
- A shaking pointer or worn movement: fit a snubber and a liquid-filled case. Check the mounting is not on a vibrating pipe.
- Reading stuck after a steam event: fit a siphon and fill it with water before commissioning.
- Zero shifted: the gauge was over-ranged. Use a higher scale or fit an overpressure protector.
- Blocked or corroded: fit a diaphragm seal or change the wetted material.
Common mistakes
- Scales chosen so that normal operation is at 90 % of the dial.
- No siphon on steam service.
- Standard cases, not safety pattern, on gas and high-pressure service.
- Small 63 mm dials where operators need to read from a distance.
- Copper-alloy wetted parts in ammonia or sour service.
- No isolation valve, so the gauge can't be changed without a shutdown.
Checklist
- The working pressure is ≤ ¾ of full scale (steady) or ≤ ⅔ (fluctuating).
- The accuracy class gives the error needed at full scale.
- The dial size suits the reading distance (100 mm or larger for process).
- The case is S3 safety pattern for gas or high pressure, or per company rule.
- The wetted parts suit the fluid. Use stainless for most process service.
- A siphon is fitted for steam, and a snubber or filling for pulsation.
- A diaphragm seal is fitted for corrosive or clogging fluids.
- An isolation valve or 2-valve manifold is fitted.
- Oxygen-service gauges are cleaned and marked accordingly.
Quick reference
- Error = class % × full scale.
- Scale: working ≤ ¾ FS (steady), ≤ ⅔ FS (fluctuating).
- Standard scales: 1, 1.6, 2.5, 4, 6, 10, 16, 25, 40, 60, 100 bar…
- S3: solid front, blow-out back.
- Accessories: siphon (steam), snubber or filling (pulsation), seal (corrosive), protector (over-range).
Further reading
- EN 837-1, Pressure gauges: Bourdon tube pressure gauges
- EN 837-2, Pressure gauges: selection and installation recommendations
- EN 837-3, Pressure gauges: diaphragm and capsule pressure gauges
- In this series: 1.4 Accuracy and range · 2.4 Diaphragm seals · next, 2.6 Impulse lines
The selection rules follow EN 837-2 as commonly applied. Confirm against the edition used by your project and the company's gauge specification. EN is named for identification only.