Pressure · 2.6

Impulse lines: slopes, sealing, and gas versus liquid installation

26 October 2026 · 9 min read · ISO 2186

In short

Many "bad transmitters" are good transmitters connected through a bad impulse line. The tubing between the tapping and the instrument is part of the measurement. If it holds a bubble, a slug of condensate or a leg of different density, the transmitter faithfully measures the error.

Where this matters

How it works

Each leg of an impulse line adds its own hydrostatic head:

ΔPerror = (ρH leg × hH − ρL leg × hL) × g

ρ is the density of what actually fills each leg (kg/m³), h is the vertical height of the leg (m) and g = 9.80665 m/s². If both legs hold the same fluid at the same height and temperature, the heads cancel. Any difference in fill, height or temperature becomes a measurement error.

Installation by fluid

FluidTapping orientationTransmitter positionWhy
LiquidSide of the pipe, horizontal or up to 45° belowBelow the tappingsGas bubbles rise back to the pipe. Sediment stays out of the tapping.
GasTop of the pipe, or up to 45° aboveAbove the tappingsCondensate drains back to the pipe.
SteamSide of the pipeBelow, with condensate (seal) pots or tees at equal heightBoth legs fill with condensate at equal height. The cold water protects the transmitter.

What the standards and practice say

Worked example: two impulse-line faults on an orifice meter

InputValue
ServiceWater, orifice DP range 0–250 mbar
Transmitter1 m below the tappings

Fault 1, gas trapped in the low-pressure leg. A 1 m vertical section of the low leg holds gas instead of water. The low side loses that head: ΔPerror = 1,000 × 9.80665 × 1 = 9,807 Pa = 98 mbar. The transmitter reads 98 mbar too high.

As a share of span, 98 / 250 = 39 %. Because flow ∝ √DP, at a true DP of 100 mbar the meter would read √(198/100) = 1.41 times the true flow, 41 % high.

Fault 2, one leg warmer than the other. Hot water in one leg (958 kg/m³, near 100 °C) and cooler water in the other (1,000 kg/m³), over 0.5 m: (1,000 − 958) × 9.80665 × 0.5 = 206 Pa = 2.1 mbar, which is 0.8 % of span. It is smaller, but it changes with the weather and the process temperature.

FaultError% of 250 mbar span
1 m gas pocket in a liquid leg98 mbar39 %
0.5 m of legs at different temperatures2.1 mbar0.8 %
Correct installation, legs together, vented≈ 00 %

What this example shows

When it fails: the fixes in order

  1. Vent or drain both legs and re-zero at line pressure (article 2.3).
  2. Correct the orientation: transmitter below for liquid and steam, above for gas.
  3. Remove pockets: re-slope the lines and add vents or drains at unavoidable high or low points.
  4. Shorten: close-couple or direct-mount the transmitter.
  5. Heat-trace or insulate both legs together where needed.

Common mistakes

Checklist

Quick reference

Further reading

The densities are typical values for water. Use the project fluid's properties at line conditions for real calculations, and the company's hook-up standards for installation details. ISO is named for identification only.